The PK5508 keypad works with the following control panels: PowerSeries Control Panel PC1616. User Manual - PowerSeries - PC1616/1832/1864 - V4.6; User Manual PC1616-1832-1864 v4-7 - CHI. DSC (Digital Security Controls) is a world leader in electronic security. Since the company’s genesis, the experts at DSC have been leading the way. User Manual. W A R N I N G †. The entire manual should be carefully read. Software Version 2.4ZD ™ IMPORTANT - READ CAREFULLY: DSC Software purchased with or without Products and Components is copyrighted and is purchased under the following license terms:. This End-User License Agreement (“EULA”) is a legal agreement between.
PC1616/PC1832/PC1864 STANDARD INSTALLATION GUIDE
This Installation Guide provides the basic installation, wiring and programming information required to program the PowerSeries PC1616,
PC1832 and PC1864 control panels.
PC1832 and PC1864 control panels.
This guide shall be used in conjunction with the PowerSeries PC1616/1832/1864 Reference Manual
which can be obtained from your local dealer or downloaded from the DSC web site at www.dsc.com.
NOTE: All necessary information required to meet UL Listing requirements is contained in this document.
Read the complete guide, then work through each step as indicated.
FEATURES
PC1616
PC1832
PC1864
OUT Of THE BOX
On-board Zones
6
8
8
Qty 1
❑
Qty 1
❑
Qty 1
❑
Qty 1
❑
Qty 2
❑
Qty 1
❑
Qty 4
❑
Qty 16
❑
Qty 1
❑
Qty 1
❑
Qty 1
❑
Qty 1
❑
Cabinet
PC Module
Installation guide
User manual
Cabinet Label
Cabinet Door Plug
Standoffs
5.6K
PC Module
Installation guide
User manual
Cabinet Label
Cabinet Door Plug
Standoffs
5.6K
Ω Resistors
2.2K
Ω Resistors
1.0K
Ω Resistors
10
Ω Resistors
Grounding Kit
Hardwired Zones
16 (1xPC5108)
32(3xPC5108)
64 (7xPC5108)
Wireless Zones
16
32
32
Keypad Zone Support
✔
✔
✔
On-board PGM Outputs
PGM 1 - 50mA
PGM 2 - 300mA
PGM 2 - 300mA
PGM 1 - 50mA
PGM 2 - 300mA
PGM 2 - 300mA
PGM 1, 3, 4 - 50mA
PGM 2 - 300mA
PGM 2 - 300mA
PGM Expansion
8x50mA (PC5208)
4x500 mA (PC5204)
4x500 mA (PC5204)
8x50mA (PC5208)
4x500 mA (PC5204)
4x500 mA (PC5204)
8x50mA (PC5208)
4x500 mA (PC5204)
4x500 mA (PC5204)
Keypads
8
8
8
Partitions
2
4
8
SPECIFICATIONS
Temp Range ....... 0°C-49°C (32°F-120°F)
Humidity (Max)........................... 93%R.H.
Power Supply........ 16.5V
Humidity (Max)........................... 93%R.H.
Power Supply........ 16.5V
AC
/40VA @60Hz
Current Draw (Panel) .........110mA (nom.)
Aux+ Output............11.1-12.6V
Aux+ Output............11.1-12.6V
DC
/700mA
Bell Output ..............11.1-12.6V
DC
/700mA
User Codes
32 + Master Codes
32 + Master Codes
32 + Master Codes
Event Buffer
500 Events
500 Events
500 Events
Transformer Required
16.5V
AC
/40VA
16.5V
AC
/40VA
16.5V
AC
/40VA
Battery Required
4Ah / 7Ah/14AHr
4Ah / 7Ah/14AHr
4Ah / 7Ah/14AHr
Bell Output
12V/700 mA (cont)
12V/700 mA (cont)
12V/700 mA (cont)
COMPATIBLE DEVICES
Keypads (
Backward compatible with all PowerSeries keypads)
Modules
PK5500 Keypad...........................................................125mA (max.)
PK5501 Keypad...........................................................125mA (max.)
PK5508 LED Keypad...................................................125mA (max.)
PK5516 LED Keypad...................................................125mA (max.)
PC5532Z LED Keypad ................................................125mA (max.)
LCD5511 Fixed Message LCD Keypad........................ 85mA (max.)
LED5511Z 8-zone LED Keypad .................................100mA (max.)
PK5501 Keypad...........................................................125mA (max.)
PK5508 LED Keypad...................................................125mA (max.)
PK5516 LED Keypad...................................................125mA (max.)
PC5532Z LED Keypad ................................................125mA (max.)
LCD5511 Fixed Message LCD Keypad........................ 85mA (max.)
LED5511Z 8-zone LED Keypad .................................100mA (max.)
Cabinets
PC5003C ..................................... 222x298x78mm (11.3x11.7x3.0in)
PC500C ......................................... 213x235x78mm (8.4x9.25x3.0in)
PC500C ......................................... 213x235x78mm (8.4x9.25x3.0in)
Refer to the Reference Manual for alternate control cabinets
T-Link TL-250/TL300 .......................................................275/350mA
PC5100 2-wire Interface ............ 40mA plus devices to 170mA max.
PC5132-433 Wireless Receiver .............................................125mA
RF5108-433 Wireless Receiver .............................................125mA
PC5108 Zone Expander ..........................................................30mA
PC5204 Power Supply with 4 Programmable Outputs ............30mA
PC5208 Low Current Programmable Output Module ..............50mA
PC5400 Printer/DVAC Module .................................................65mA
PC5401 Bi-Directional RS232 Module (Not UL Listed) ............65mA
Escort5580 Telephone Interface Module ...............................130mA
PC5100 2-wire Interface ............ 40mA plus devices to 170mA max.
PC5132-433 Wireless Receiver .............................................125mA
RF5108-433 Wireless Receiver .............................................125mA
PC5108 Zone Expander ..........................................................30mA
PC5204 Power Supply with 4 Programmable Outputs ............30mA
PC5208 Low Current Programmable Output Module ..............50mA
PC5400 Printer/DVAC Module .................................................65mA
PC5401 Bi-Directional RS232 Module (Not UL Listed) ............65mA
Escort5580 Telephone Interface Module ...............................130mA
Refer to the Reference Manual for additional devices.
Classified in Accordance with ANSI/SIA CP-01-2000 (SIA-FAR)
2 9 0 0 7 1 0 9 R0 0 3
Advertising
This manual is related to the following products:
Popular Brands
Popular manuals
Advertising
UL Listed Commercial and Residential Installations
The installation requirements listed below must be met for the following
grades of service.
Grade AA Central Station and Police Connect (Standard or Encrypted Line
Security Service)
The installation must use T-Link module which communicates over LAN/WAN to
the Sur-Gard MLR-IP receiver or the TL200/250 which communicates over LAN/
WAN/Internet to the SG System III receiver. Polling time must be 90 seconds. Com-
promise detection time must be 6 minutes.
Grade A Local
•The installation must have a bell which is UL Listed for mercantile local alarms
grades of service.
Grade AA Central Station and Police Connect (Standard or Encrypted Line
Security Service)
The installation must use T-Link module which communicates over LAN/WAN to
the Sur-Gard MLR-IP receiver or the TL200/250 which communicates over LAN/
WAN/Internet to the SG System III receiver. Polling time must be 90 seconds. Com-
promise detection time must be 6 minutes.
Grade A Local
•The installation must have a bell which is UL Listed for mercantile local alarms
(AMSECO MBL10B with model AB-12 bell housing).
•The digital communicator must be enabled.
•The control panel must be in the attack-resistant enclosure (DSC Model CMC-1
•The control panel must be in the attack-resistant enclosure (DSC Model CMC-1
or PC4050CAR).
Grade B Central Station and Police Connect
•The installation must have a bell which is UL Listed for mercantile local alarms
•The installation must have a bell which is UL Listed for mercantile local alarms
(AMSECO MBL10B with model AB-12 bell housing).
•The digital communicator must be enabled.
•The control panel must be in the attack resistant enclosure (DSC Model CMC-1
•The control panel must be in the attack resistant enclosure (DSC Model CMC-1
or PC4050CAR).
Grade C Central Station
•The digital communicator must be enabled.
•The control panel must be in the attack resistant enclosure (DSC Model CMC-1
•The digital communicator must be enabled.
•The control panel must be in the attack resistant enclosure (DSC Model CMC-1
or PC4050CAR).
All Commercial Installations
•The Entry Delay must not exceed 120 seconds
•The Exit Delay must not exceed 120 seconds.
•The minimum Bell Time-out is 15 minutes.
Residential Fire & Burglary Installations
•The Entry Delay must not exceed 45 seconds
•The Exit Delay must not exceed 60 seconds.
•The minimum Bell Time-out is 4 minutes.
Home Health Care Signaling Equipment
•There must be at least two keypads, one of either the LCD5500Z/LCD5520Z or
•The Entry Delay must not exceed 120 seconds
•The Exit Delay must not exceed 120 seconds.
•The minimum Bell Time-out is 15 minutes.
Residential Fire & Burglary Installations
•The Entry Delay must not exceed 45 seconds
•The Exit Delay must not exceed 60 seconds.
•The minimum Bell Time-out is 4 minutes.
Home Health Care Signaling Equipment
•There must be at least two keypads, one of either the LCD5500Z/LCD5520Z or
LCD5501Z and one of the following models, PC5508Z, PC5516Z or PC5532Z.
•Each system shall be programmed to activate an audible Trouble signal within 90
seconds upon loss of microprocessor memory.
•The minimum Bell Time-out is 5 minutes.
Programming
The notes in the programming sections describing the system configurations for
UL Listed installations must be implemented.
Control of the Protected Premises
In order to have a UL Certificated system the protected area is to be under the
responsibility of one ownership and management (i.e., one business under one
name). This may be a group of buildings attached or unattached with different
addresses but under the responsibility of someone having mutual interest. The
person of mutual interest is not the alarm-installing company.
Bell Location
The alarm sounding device (bell) must be located where it can be heard by the
person or persons responsible for maintaining the security system during the daily
arming cycle.
Protection of the Control Unit
The local control and the local power supply must be protected in one of the fol-
lowing ways:
•The control unit and audible alarm device must be in a protected area which is
Programming
The notes in the programming sections describing the system configurations for
UL Listed installations must be implemented.
Control of the Protected Premises
In order to have a UL Certificated system the protected area is to be under the
responsibility of one ownership and management (i.e., one business under one
name). This may be a group of buildings attached or unattached with different
addresses but under the responsibility of someone having mutual interest. The
person of mutual interest is not the alarm-installing company.
Bell Location
The alarm sounding device (bell) must be located where it can be heard by the
person or persons responsible for maintaining the security system during the daily
arming cycle.
Protection of the Control Unit
The local control and the local power supply must be protected in one of the fol-
lowing ways:
•The control unit and audible alarm device must be in a protected area which is
armed 24 hours a day.
•Each partition must arm the area protecting the control unit and the audible
alarm device power supply. This may require duplicate protection armed by each
partition. Access to this protected area, without causing an alarm, will require
that all partitions be disarmed.
partition. Access to this protected area, without causing an alarm, will require
that all partitions be disarmed.
•In all cases described above, the protected area for the control unit must be pro-
grammed as not-bypassable.
Casual Users
The installer should caution the user(s) not to give system information to casual
users (e.g. codes, bypass methods, etc. to baby-sitters or service people). Only the
One-Time Use codes should be given to casual users.
The installer should caution the user(s) not to give system information to casual
users (e.g. codes, bypass methods, etc. to baby-sitters or service people). Only the
One-Time Use codes should be given to casual users.
User Information
The installer should advise the users and note in the User’s Manual:
•Service organization name and telephone number
•The programmed exit time
•The programmed entry time
•Test system weekly
Two-Wire Smoke Detector Compatibility (if available)
Maximum loop resistance: 24 Ohms
•Operating Voltage Range: 9.8 - 13.8 V
The installer should advise the users and note in the User’s Manual:
•Service organization name and telephone number
•The programmed exit time
•The programmed entry time
•Test system weekly
Two-Wire Smoke Detector Compatibility (if available)
Maximum loop resistance: 24 Ohms
•Operating Voltage Range: 9.8 - 13.8 V
DC
•Maximum Alarm Current: 89 mA
•Compatibility Identifier: PC18-1
See Section 5PGM Wiring for compatible 2-wire smoke detectors.
•Compatibility Identifier: PC18-1
See Section 5PGM Wiring for compatible 2-wire smoke detectors.
SIA FAR Installations
Minimum requirement system for SIA-FAR Installations:
• 1 PC1616/PC1832/PC1864 Control panel
• 2 Local annunciation devices
• 2 Local annunciation devices
The local annunciation devices may be any combination of the following keypads,
as long as there is at least one LCD keypad in the installation (Model LCD5500Z or
PK5500).
as long as there is at least one LCD keypad in the installation (Model LCD5500Z or
PK5500).
• LCD5500Z
• LCD5501Z
• PK5500
• PK5508
• PKP-LCD
• PKP-ICN
• PK5501
• PK5516
The following optional subassembly modules also bear the SIA FAR classification
and may be used if desired:
and may be used if desired:
PC5108 Zone Expander Module
Compatible initiating devices: Bravo200 series, 300 series, 400 series, 500 series,
600 series, AC-100, Encore300 series, Force200 series, 210 series, MN240.
Compatible initiating devices: Bravo200 series, 300 series, 400 series, 500 series,
600 series, AC-100, Encore300 series, Force200 series, 210 series, MN240.
PC5208 Low Current PGM Output Module
The following optional accessory modules also bear the SIA FAR classification and
may be used if desired.
PC5204 Auxiliary Power Supply with PGM output ports
Escort5580/Escort5580TC, PC5400 Printer Module
The following optional accessory modules also bear the SIA FAR classification and
may be used if desired.
PC5204 Auxiliary Power Supply with PGM output ports
Escort5580/Escort5580TC, PC5400 Printer Module
Caution
• For SIA FAR installations, only use modules / devices that are listed on this page.
• Fire Alarm Verification feature (Auto Verified Fire zone) is not supported on 2-
• Fire Alarm Verification feature (Auto Verified Fire zone) is not supported on 2-
wire smoke detectors zones. This feature may be enabled for 4-wire smoke
detectors only.
detectors only.
• Call Waiting Cancel (Section 382 Option 4) feature on a non-Call Waiting line
will prevent successful communication to the central station.
• All smoke detectors on the system must be tested annually by conducting the
Installer Walk Test prior to exiting the walk test mode, a sensor reset must be
conducted on the system, [
conducted on the system, [
✱][7][2] to reset all latching 4-wire smoke detectors.
Dsc Pk5501 Programming Manual
Please refer to the smoke detector installation instructions on how to correctly
test the detectors.
test the detectors.
Notes
• Programming at installation may be subordinate to other UL requirements for
the intended application.
• Cross zones have the ability to individually protect the intended area (e.g.,
motion detectors, which overlap).
• Cross zoning is not recommended for line security Installations nor is it to be
implemented on exit / entry zones.
• There is a communication delay of 30 seconds in this control panel. It can be
removed, or it can be increased up to 45 seconds at the option of the end user
by consulting with the Installer.
by consulting with the Installer.
• Do not duplicate any reporting codes. This applies for all communication for-
mats other than SIA sending automatic programmed reporting codes.
• The control unit must be installed with a local sounding device and an off-
premise transmission for SIA communication format.
• For ULC Listed Fire Monitoring Installations & module requirements, please refer
to the ULC Installation Information sheet, part# 29002157.
• Use a CSA/cUL transformer, hardwired.
• All tamper circuits may be connected to the same zone.
• Use ULC-LA for AC Power indication.
• All tamper circuits may be connected to the same zone.
• Use ULC-LA for AC Power indication.
LISTING REQUIREMENTS